What is composite grating and why does the load table matter?
Composite grating, or FRP grating (also known as fiberglass grating and composite flooring), is an open-mesh panel of glass fiber and resin used as flooring for platforms, walkways, stairs, trench covers and access platforms in the oil and gas, petrochemical, water and wastewater treatment, power and marine industries. Light weight, complete corrosion resistance, electrical insulation and an anti-slip surface make this composite flooring an attractive alternative to steel grating.
However, the stiffness of composite grating is about one fifteenth to one twentieth that of steel. So in designing composite flooring, deflection (deformation), not strength, is usually the governing criterion: a panel that easily carries the load in terms of strength may bend too much underfoot and feel unsafe. The load table, or load capacity table, answers exactly this question: for each grating thickness and each support span, how much deflection occurs under a given load, and is that deflection within the allowable limit?
Types of composite grating: molded and pultruded
There are two main types of FRP grating on the market, with different load-bearing behavior, and a separate load capacity table is prepared for each:
| Feature | Molded grating | Pultruded grating |
|---|---|---|
| Manufacturing method | Continuous fibers laid in a grid mold and impregnated with resin as a single piece | Pultruded load-bearing bars (I or T section) assembled with cross bars |
| Glass fiber weight fraction | About 30 to 35 percent | About 60 to 70 percent in the load-bearing bars |
| Load-bearing direction | Almost two-way; can carry load in both directions | One-way; load capacity only in the direction of the load-bearing bars |
| Achievable span | Short to medium | Longer at the same thickness |
| Corrosion and impact resistance | Excellent, thanks to higher resin content | Good |
| Common use | Chemical platforms, basin floors, trench covers, corrosive environments | Long-span walkways and platforms, footbridges |
Key terms in composite flooring load tables
| Term | Engineering definition | Unit |
|---|---|---|
| Span | Center-to-center distance between two supports in the direction of the main load-bearing bars | mm |
| Depth | Overall height of the grating panel; the most important factor in load capacity | mm |
| Mesh | Grid opening size, such as 38×38 or 50×50 mm | mm |
| Uniform distributed load (U) | Load spread evenly over the whole surface | kN/m² (1 kN/m² is about 102 kg/m²) |
| Concentrated load (C) | Load applied as a line load at midspan across the full panel width, or on a small area (e.g. 100×100 or 300×300 mm) | kN per meter width, or kN |
| Deflection (D) | Maximum vertical deformation of the panel at midspan | mm |
| Deflection limit | Maximum acceptable deflection; common criterion: L/200 and at most about 10 mm for pedestrian flooring | mm |
| Ultimate load | The load at which the panel fails; usually several times the allowable working load | kN |
Engineering basis of the grating load capacity table
Composite grating load tables are prepared from beam theory and load tests. For a panel on two simple supports (single span), midspan deflection is calculated from:
where q is the uniform load per unit width, P the concentrated load per unit width, L the span, E the effective flexural modulus of the composite and I the moment of inertia of the load-bearing bars per meter of width. For load-bearing bars of thickness t and height h:
- Effect of span: deflection under uniform load increases with the fourth power of the span. Doubling the span multiplies deflection by 16. That is why reducing the spacing of the supporting beams is the most effective way to increase the load capacity of composite flooring.
- Effect of thickness: stiffness increases with the cube of the height of the load-bearing bars. Increasing grating thickness from 38 to 50 mm raises stiffness by about 2.3 times.
At short spans and large thicknesses, shear deformation in the grating grid also makes a significant contribution. That is why manufacturers' official load capacity tables are prepared or calibrated from actual load tests on panels, and the relations above are used to understand the behavior and for initial estimates.
Design loads for composite flooring by application
Before consulting the load table, the design load must be defined. The values below are based on common classifications of floor live loads (such as EN 1991-1-1) and experience of industrial projects; final values must be set according to each project's code and technical specifications:
| Composite flooring application | Typical uniform load (kN/m²) | Typical concentrated load | Typical deflection criterion |
|---|---|---|---|
| Light access and maintenance walkways | 2.5 | About 1.5 to 2 kN | L/200 and max. 10 mm |
| Industrial platforms and public walkways | 5 | About 3 to 4.5 kN | L/200 and max. 10 mm |
| Heavy industrial platforms and storage areas | 7.5 to 10 | About 4.5 to 7 kN | L/200 or stricter |
| Trolley, forklift and vehicle traffic | Requires special design based on wheel load and contact area | Per project specification | |
Sample load table for molded composite grating
The tables below show midspan deflection (in mm) for three common thicknesses of molded fiberglass grating with a mesh of about 38×38 mm, under uniform load and concentrated line load. Cells where deflection exceeds the allowable limit (L/200 and at most 10 mm) are marked with ✕ in red.
Composite grating, 25 mm thick
| Span (mm) | Uniform distributed load (kN/m²) | Concentrated line load at midspan (kN per meter width) | Deflection limit (mm) | |||||
|---|---|---|---|---|---|---|---|---|
| 2.5 | 5 | 7.5 | 10 | 1.5 | 3 | 4.5 | ||
| 500 | 1.0 | 2.1 | 3.1 ✕ | 4.2 ✕ | 2.0 | 4.0 ✕ | 6.0 ✕ | 2.5 |
| 750 | 5.3 ✕ | 10.6 ✕ | 15.9 ✕ | 21.2 ✕ | 6.8 ✕ | 13.5 ✕ | 20.3 ✕ | 3.8 |
| 1000 | 16.7 ✕ | 33.4 ✕ | 50.2 ✕ | 66.9 ✕ | 16.1 ✕ | 32.1 ✕ | 48.2 ✕ | 5.0 |
| 1250 | 40.8 ✕ | 81.7 ✕ | 122.5 ✕ | 163.3 ✕ | 31.4 ✕ | 62.7 ✕ | 94.1 ✕ | 6.2 |
| 1500 | 84.7 ✕ | 169.3 ✕ | 254.0 ✕ | 338.6 ✕ | 54.2 ✕ | 108.4 ✕ | 162.5 ✕ | 7.5 |
Composite grating, 38 mm thick
| Span (mm) | Uniform distributed load (kN/m²) | Concentrated line load at midspan (kN per meter width) | Deflection limit (mm) | |||||
|---|---|---|---|---|---|---|---|---|
| 2.5 | 5 | 7.5 | 10 | 1.5 | 3 | 4.5 | ||
| 500 | 0.3 | 0.6 | 0.9 | 1.2 | 0.6 | 1.1 | 1.7 | 2.5 |
| 750 | 1.5 | 3.0 | 4.5 ✕ | 6.0 ✕ | 1.9 | 3.9 ✕ | 5.8 ✕ | 3.8 |
| 1000 | 4.8 | 9.5 ✕ | 14.3 ✕ | 19.0 ✕ | 4.6 | 9.1 ✕ | 13.7 ✕ | 5.0 |
| 1250 | 11.6 ✕ | 23.3 ✕ | 34.9 ✕ | 46.5 ✕ | 8.9 ✕ | 17.9 ✕ | 26.8 ✕ | 6.2 |
| 1500 | 24.1 ✕ | 48.2 ✕ | 72.3 ✕ | 96.4 ✕ | 15.4 ✕ | 30.9 ✕ | 46.3 ✕ | 7.5 |
Composite grating, 50 mm thick
| Span (mm) | Uniform distributed load (kN/m²) | Concentrated line load at midspan (kN per meter width) | Deflection limit (mm) | |||||
|---|---|---|---|---|---|---|---|---|
| 2.5 | 5 | 7.5 | 10 | 1.5 | 3 | 4.5 | ||
| 500 | 0.1 | 0.3 | 0.4 | 0.5 | 0.3 | 0.5 | 0.8 | 2.5 |
| 750 | 0.7 | 1.3 | 2.0 | 2.6 | 0.8 | 1.7 | 2.5 | 3.8 |
| 1000 | 2.1 | 4.2 | 6.3 ✕ | 8.4 ✕ | 2.0 | 4.0 | 6.0 ✕ | 5.0 |
| 1250 | 5.1 | 10.2 ✕ | 15.3 ✕ | 20.4 ✕ | 3.9 | 7.8 ✕ | 11.8 ✕ | 6.2 |
| 1500 | 10.6 ✕ | 21.2 ✕ | 31.7 ✕ | 42.3 ✕ | 6.8 | 13.5 ✕ | 20.3 ✕ | 7.5 |
Allowable span table for fiberglass grating
The table below shows the maximum span at which deflection under uniform load does not exceed L/200 (and 10 mm). It is used to set the spacing of supporting beams at the preliminary design stage:
| Grating thickness | Load 2.5 kN/m² | Load 5 kN/m² | Load 7.5 kN/m² | Load 10 kN/m² |
|---|---|---|---|---|
| 25 mm | 669 mm | 531 mm | 464 mm | 421 mm |
| 38 mm | 1016 mm | 807 mm | 705 mm | 640 mm |
| 50 mm | 1337 mm | 1061 mm | 927 mm | 842 mm |
Deflection of composite grating under a 5 kN/m² uniform load versus span
As the chart shows, deflection rises very rapidly with span (fourth power). The point where each curve crosses the dashed deflection limit line shows the allowable span for that grating thickness at this load.
Practical example: selecting FRP grating with the load table
Problem: an industrial platform is designed for a uniform load of 5 kN/m² and a concentrated load of 3 kN per meter width. The supporting beams are 750 mm apart. Which composite grating thickness is suitable?
- Deflection limit: L/200 = 750 ÷ 200 = 3.75 mm
- 38 mm, uniform load: deflection 3.0 mm ✓
- 38 mm, concentrated load: deflection 3.9 mm ✕
- 50 mm, uniform load: deflection 1.3 mm ✓
- 50 mm, concentrated load: deflection 1.7 mm ✓
- Result: 50 mm grating, or a shorter span for 38 mm
This example makes an important point: at short and medium spans, the concentrated load often governs, not the uniform load. Had the designer checked only the uniform load, they would have chosen 38 mm grating, whose deflection under the concentrated load exceeds the limit. The alternative is to reduce the beam spacing to about 700 mm or to lay the panels continuously over several supports.
Factors that reduce the load capacity of composite flooring
FRP grating load tables are usually prepared for standard conditions. The following factors reduce actual capacity and must be considered in design:
| Factor | Effect on composite grating | Design recommendation |
|---|---|---|
| High service temperature | Reduced resin modulus and strength as the heat deflection temperature is approached | Above about 50 to 60 °C, apply a capacity reduction factor or choose a heat-resistant resin |
| Permanent load (creep) | Gradual increase in deflection over time | For permanent loads such as fixed equipment, calculate long-term deflection with a creep factor |
| Cut-outs and openings in the panel | Load-bearing bars cut and local loss of capacity | Reinforce around the opening with edge banding or an auxiliary joist |
| Short bearing length | Edge crushing and panel slipping | Provide sufficient bearing length on the support (usually at least about 25 to 40 mm) |
| Chemical environment and UV | Gradual loss of surface properties | Choose a suitable resin (isophthalic, vinyl ester or phenolic) and a UV-resistant coating |
| Cantilever | Large deflection at the free edge | Limit cantilever length and check it separately |
Safety factor and load testing of grating
In composite grating, the failure (ultimate) load is usually several times the allowable working load, and because deflection governs, a panel that meets the deflection requirements usually has a high margin of safety against failure. However, because of the brittle behavior of composites (no yield before failure, unlike steel) and the effect of creep, design must use appropriate safety factors. Grating load capacity is determined by flexural load tests on complete panels (uniform loading with sandbags or a hydraulic jack and concentrated loading on a steel plate), with deflection measured by dial gauge or displacement sensor. Standards such as BS 4592-4 for composite open-mesh flooring and loading codes such as EN 1991-1-1 are the references for loads and acceptance criteria.
Installation tips for achieving the tabulated load capacity
- Panel orientation: in pultruded grating, the load-bearing bars must run perpendicular to the supporting beams; installing the panel the wrong way round severely reduces capacity.
- Hold-down clips: fix panels to the supports with special clips (M- or C-shaped stainless steel clips) so they do not move under vibration or wind; usually at least at each panel corner and at regular intervals.
- Level supports: uneven beams cause unequal bearing and stress concentration.
- Cutting and sealing: seal cut edges of the grating with resin. Full details are in the article cutting and machining composite parts.
- Handling and storage: store panels on a flat surface on level supports.
Comparing composite grating with steel grating
| Criterion | Composite (FRP) grating | Galvanized steel grating |
|---|---|---|
| Weight | About one third to one quarter | Heavy |
| Corrosion resistance | Excellent; maintenance-free | Requires galvanizing and periodic repair |
| Stiffness (deflection) | Lower; deflection governs design | High |
| Electrically insulating and non-sparking | Yes | No |
| Anti-slip surface | Integral grit or concave surface | Serrated |
| Installation and on-site cutting | Easy with simple tools | Requires hot cutting and welding |
Composite grating and load capacity tables at Nabak Composite
Nabak Composite supplies FRP grating and composite flooring in various thicknesses, meshes and colors. For each project, given the uniform load, concentrated load, beam spacing and environmental conditions, our team recommends the right grating thickness and type based on the product's tested load capacity table. To learn about methods for predicting the mechanical properties of composites, read the article predicting the properties of polymer composites.
Frequently asked questions about composite grating load tables
What information does a composite grating load table give?
A composite grating load table shows how much each grating thickness deflects at each support span under a given uniform or concentrated load, and whether that deflection is within the allowable limit.
What is the allowable deflection of FRP grating?
The common criterion for pedestrian flooring is deflection less than one two-hundredth of the span (L/200) and at most about 10 mm; a stricter criterion is chosen for sensitive applications.
What is the difference between uniform and concentrated load in a load table?
A uniform load in kN/m² is spread over the whole grating surface; a concentrated load is applied as a line load at midspan across the full panel width, or on a small area, and usually causes more deflection at short spans.
How is the span of composite grating measured?
The span is the distance between support centers in the direction of the grating's main load-bearing bars. In pultruded grating, panel orientation is very important, because load capacity is high only in the direction of the load-bearing bars.
Are load table values valid at high temperatures?
No. Load tables are usually prepared for ambient temperature and short-term loads. At high temperatures, under permanent loads (creep effect) and in chemical environments, capacity reduction factors must be applied.
Summary
The load capacity table is the common language of the designer and the composite grating manufacturer. In composite flooring, deflection almost always governs and varies with the fourth power of span and the cube of thickness; choosing the right grating thickness and beam spacing is therefore the key to an economical and safe design. When using the load table, check both uniform and concentrated loads, consider the effects of temperature, creep, openings and grating type (molded or pultruded), and always use the product's tested table. For product load capacity tables and advice on choosing the right FRP grating for your project, contact the Nabak Composite team.