FRP/GFRP Composite Cable Tray – Technical Datasheet | Nabak Composite
دیتاشیت محصولات

FRP/GFRP Composite Cable Tray – Technical Datasheet | Nabak Composite

مقاله1405/08/12English
مشاهده‌ی آنلاین سند

FRP / GFRP Composite Cable Tray Technical Datasheet — GFRP Cable Tray and Fiberglass Cable Ladder by Nabak Composite

Cover of the FRP composite cable tray technical datasheet by Nabak Composite - FRP / GRP Cable Tray, code NBK-TDS-CT-01
TECHNICAL DATA SHEET

FRP Composite Cable Tray

Perforated, solid-bottom and ladder cable tray dimensions and safe working loads, NEMA FG-1 load classes, fire and chemical resistance, section, allowable-load and fill formulas, fittings and an installation guide

NBK-TDS-CT-01-ENRev 1.0  ·  2026
FRP / GFRP Composite Cable Tray – Technical DatasheetIntroduction, Types & Advantages  |  Page 1 of 5

The Nabak Composite FRP composite cable tray (FRP / GRP Cable Tray) is a cable support and routing system made of pultruded GFRP composite with flame-retardant resin: an electrically insulating, corrosion-proof, lightweight cable tray that needs no galvanizing or paint and replaces galvanized steel, stainless steel and aluminum cable trays in corrosive, humid and marine environments.

50 – 600 mmcable tray width
50 / 100 / 150 mmside height
≤ 25ASTM E84 flame spread
3000 / 6000 mmstandard section length

What Is an FRP Composite Cable Tray (GFRP Cable Tray)?

The composite cable tray, also known as FRP cable tray, GFRP cable tray, fiberglass cable tray, composite cable trunking and FRP Cable Tray, is produced by the pultrusion process: continuous glass fiber together with mat and cross-direction fabrics is drawn through a bath of flame-retardant polyester or vinyl ester resin and cured in a heated die into the channel shape of the cable tray. Ventilation and drainage holes in the floor and sides are then punched or CNC-cut into the body of the FRP cable tray.

FRP is the generic name for fiber-reinforced polymers, and GFRP (or GRP) is FRP composite reinforced with glass fiber. Together with a full range of fittings (bends, tees, crosses, reducers, splice plates and covers) and composite or stainless steel supports and clamps, the Nabak composite cable tray forms an integrated, corrosion-proof cabling system that complements composite grating, FRP handrail and GFRP structures in an industrial plant.

Types of Nabak Composite FRP Cable Tray

Perforated cable trayThe most common FRP cable tray, with ventilation holes in the floor and sides for cooling and drainage
Solid-bottom cable trayGFRP cable tray without perforations for protecting instrumentation and telecom cables
Composite cable ladderTwo side rails with cross rungs; for heavy power cables and long spans
Channel and trunkingNarrow FRP cable tray for small routes and branches
Cable tray coverFlat or peaked composite cover for protection against sun, rain and falling debris
Fittings and accessoriesBends, tees, reducers, expansion splices, brackets and GFRP clamps

Advantages of FRP Cable Tray

  • Corrosion-proof: composite cable tray does not rust in acids, chlorine, seawater and chemical vapors; no galvanizing or paint is needed.
  • Electrically insulating and non-magnetic: GFRP cable tray reduces the risk of electric shock from contact with a damaged cable and has no induced current.
  • Lightweight and easy to install: the density of fiberglass cable tray is about one quarter of steel, so handling and installation are easy; it is cut with a diamond-blade saw and needs no welding.
  • Flame-retardant, low smoke: flame-retardant resin with a flame spread index ≤ 25 and self-extinguishing behavior.
  • UV-stable: surface veil and UV-inhibiting additive for open routes.
  • Low life-cycle cost: a decades-long service life of FRP cable tray in corrosive environments, with no repair or replacement.
composite cable tray | FRP cable tray | GFRP cable traynabakcomposite.com  |  +98 21 4881 2124  |  @nabak.composite
FRP / GFRP Composite Cable Tray – Technical DatasheetDimension, Weight and Load Tables  |  Page 2 of 5

Dimensions and Capacity Table of Composite Cable Tray

Table 1 — Dimensions, weight and safe working load (SWL) of perforated FRP cable tray on a simple span
Width × side (mm)Thickness (mm)Cross-section area (mm²)Moment of inertia I (mm⁴)Weight (kg/m)SWL, 2 m span (kg/m)SWL, 3 m span (kg/m)
100 × 5036722.38×10⁵1.244012
150 × 5038222.73×10⁵1.524513
200 × 5039722.97×10⁵1.804915
200 × 100312721.63×10⁶2.3527281
300 × 100420882.42×10⁶3.86403119
400 × 100424882.62×10⁶4.60435129
500 × 100536003.39×10⁶6.66564167
600 × 100541003.52×10⁶7.58586173
600 × 150546001.02×10⁷8.511439501

The allowable load is calculated with formulas 3 and 4 (page 4): the lower of two limits — the deflection limit L/100 (IEC 61537 criterion) and the allowable stress σu/2.5, with E = 17 GPa, ρ = 1.85 g/cm³ and a 15 mm return flange. For trays with a 50 mm side, deflection governs and a span of 1.5 to 2 m is recommended. The table is a calculation example, and the final allowable load of each FRP cable tray is confirmed by load testing for every order.

Specifications of Cable Ladder and Composite Cover

Table 2 — Common dimensions of FRP cable ladders and cable tray covers
PartCommon dimensions (mm)Thickness (mm)Description
Cable ladder side railheight 100 / 150, flange width 404 – 6Pultruded GFRP C-profile
Cross rungspacing 225 or 3003 – 4Hat or channel composite section; riveted or bonded to the rail
Cable ladder inside width300 – 900—Section length 3000 and 6000
Flat coversame width as the tray2 – 3Fixed with stainless steel clips or composite clamps
Peaked coversame width as the tray2 – 3Prevents the accumulation of water, snow and falling debris

Color and Resin of FRP Cable Tray

The standard color of the Nabak Composite cable tray is yellow, and gray and black can also be ordered. FRP cable tray is produced with flame-retardant isophthalic polyester resin for general use, flame-retardant vinyl ester for severely chemical environments and phenolic for tunnels and offshore platforms with low smoke and toxicity requirements.

NEMA FG-1 Load Classes and Metric Equivalents

Table 3 — Common load classes of fiberglass cable tray
NEMA classSpan (ft / m)Load (lb/ft)Load (kg/m)Load (kN/m)
8A / 8B / 8C8 / 2.4450 / 75 / 10074 / 112 / 1490.73 / 1.09 / 1.46
12A / 12B / 12C12 / 3.6650 / 75 / 10074 / 112 / 1490.73 / 1.09 / 1.46
20A / 20B / 20C20 / 6.1050 / 75 / 10074 / 112 / 1490.73 / 1.09 / 1.46

Conversion: 1 lb/ft ≈ 1.488 kg/m. The load classes are quoted from common NEMA text and must be checked against the valid edition of the standard; classes for long spans are usually supplied by composite cable ladders with 150 mm rails.

Selection tip: for instrumentation and telecom cables choose a solid-bottom cable tray with a cover; for power cables that generate heat choose a perforated FRP cable tray or a composite cable ladder; and for spans over 3 m choose a 150 mm side height or a GFRP cable ladder. Size the tray width with the fill formula (formula 7) and 25% spare space for future expansion.

FRP cable tray dimensions | composite cable ladder | fiberglass cable traynabakcomposite.com  |  +98 21 4881 2124  |  @nabak.composite
FRP / GFRP Composite Cable Tray – Technical DatasheetProperties, Fire, Chemical & Standards  |  Page 3 of 5

Mechanical, Physical and Electrical Properties of GFRP Cable Tray

Table 4 — Reference properties of pultruded GFRP composite in composite cable tray
PropertyTest standardUnitLengthwise (LW)Crosswise (CW)
Glass fiber content by weightASTM D2584%50 – 60
Tensile strengthASTM D638MPa207 – 30050 – 70
Flexural strengthASTM D790MPa207 – 30070 – 100
Flexural modulusASTM D790GPa14 – 185.5 – 7
Bolt bearing strengthASTM D953MPa200 – 240140 – 170
DensityASTM D792g/cm³1.8 – 1.9
Coefficient of thermal expansionASTM D69610⁻⁶ /°C8 – 1020 – 30
Dielectric strengthASTM D149kV/mm5 – 8 (perpendicular to the wall)
Surface insulation resistanceASTM D257Ω≥ 10¹²
Continuous service temperature—°C−40 to +80 (vinyl ester up to +100)
Table 5 — Fire behavior
TestStandardFlame-retardant tray
Flame spreadASTM E84≤ 25 (Class 1)
Self-extinguishingASTM D635Self-extinguishing
Flammability ratingUL 94V-0
Oxygen indexASTM D2863≥ 30%
Smoke and toxicity (phenolic)ASTM E662Very low
Table 6 — Chemical resistance (ambient temperature)
MediumVinyl ester FRPGalvanized steel
10% HClExcellentNot suitable
25% H₂SO₄ExcellentNot suitable
10% NaOHExcellentLimited
Seawater and salt fogExcellentNot suitable
Wet chlorineExcellentNot suitable

Reference Standards for Composite Cable Tray

Table 7 — Common design and test standards for FRP cable tray
StandardSubjectKey point for GFRP cable tray
NEMA FG-1Fiberglass cable tray systemsLoad classes by span and load; for example 12A, 12B and 12C for a 12 ft (3.66 m) span and 50, 75 and 100 lb/ft
IEC 61537Cable tray and cable ladder systemsDefines the safe working load (SWL), the longitudinal deflection limit L/100 and the load and fire tests
NEC Article 392Cable tray installationRules for tray fill, grounding and support spacing
ASTM E84 / UL 94Fire behaviorFlame spread and flammability rating of the composite resin

The values in Tables 4 to 6 are common reference ranges of the FRP and GFRP composite industry and are not Nabak Composite's own laboratory results. For every project, check the valid edition of the standards.

FRP Cable Tray Compared with Metal Trays

Table 8 — Composite cable tray versus galvanized steel, stainless steel and aluminum
PropertyFRP cable trayHot-dip galvanizedStainless 316Aluminum
Density (g/cm³)1.8 – 1.97.858.02.7
Corrosion in marine and chemical environmentsNoneSevereLowModerate
Electrical conductivityInsulatingConductiveConductiveConductive
On-site installation and cuttingEasy, no welding or hot workGalvanizing needs touch-upHardEasy
Initial priceMediumLowHighMedium to high
Life-cycle cost in corrosive environmentsVery lowHighLowMedium
corrosion-proof cable tray | insulating FRP cable tray | NEMA FG-1 standardnabakcomposite.com  |  +98 21 4881 2124  |  @nabak.composite
FRP / GFRP Composite Cable Tray – Technical DatasheetSection, Allowable Load and Fill Formulas  |  Page 4 of 5

Section and Capacity Formulas of Composite Cable Tray

1. Neutral axis and moment of inertia of the channel section
ȳ = Σ Ai yiΣ Ai ,   I = Σ ( Ii + Ai di² )

Components: floor, two sides and two return flanges. Tray 300×100×4: I ≈ 2.42×10⁶ mm⁴. The stiffness of FRP cable tray comes mainly from the side height.

2. Weight per metre of cable tray
wt = ρ · A × 10⁻³   [kg/m]

300×100×4: 1.85 × 2088 × 10⁻³ ≈ 3.86 kg/m (before perforation)

3. Allowable load by deflection limit
wδ = 384 E I · δlim5 L⁴ ,   δlim = L100

300×100 with L = 2000: wδ ≈ 3.95 N/mm ≈ 403 kg/m

4. Allowable load by stress
wσ = 8 σa SL² ,   σa = σu2.5

σa ≈ 83 MPa. Allowable load of FRP cable tray = min(wδ, wσ)

5. Converting the allowable load to another span (deflection governing)
w(L2) = w(L1) · ( L1L2 )³

When deflection governs, the allowable load falls with the cube of the span. 300×100: from 2 m to 3 m → 403 × (2/3)³ ≈ 119 kg/m. Reducing the support spacing is the most effective way to increase the capacity of a composite cable tray.

Cable Load and Fill Formulas for Cable Tray

6. Cable load per metre
wc = Σ ni · mi   [kg/m] ,   wc + wt ≤ SWL

ni is the number and mi the weight per metre of cable type i. On open routes, also add the snow or ice load and an installation impact factor.

7. Allowable fill of the cable tray cross-section
Σ ni · π di²4 ≤ k · b · H
Example — 300×100 FRP cable tray, fill factor k = 0.4, Ø25 power cable weighing 1.2 kg/m: k · b · H = 0.4 × 300 × 100 = 12 000 mm² ;   Acable = π × 25² / 4 ≈ 491 mm² n ≤ 12 000 / 491 ≈ 24 cables → wc = 24 × 1.2 ≈ 28.8 kg/m With a tray weight of 3.86 kg/m, the total load is about 33 kg/m, below the allowable load of the 3 m span (119 kg/m). So in this example the fill, not the load, is the limiting factor of the composite cable tray.
FRP cable tray calculation | allowable load of composite cable tray | GFRPnabakcomposite.com  |  +98 21 4881 2124  |  @nabak.composite
FRP / GFRP Composite Cable Tray – Technical DatasheetFittings, Installation & Applications  |  Page 5 of 5

Joint, Expansion and Weight Formulas

8. Spacing of expansion joints
Lj = gα · ΔT

g is the gap of the expansion splice plate. g = 25 mm, α = 9×10⁻⁶, ΔT = 50 °C → Lj ≈ 55 m (steel with α = 12×10⁻⁶ ≈ 42 m)

9. Bearing capacity of the splice bolts
Fb = n · d · t · σbrFS

4 × M10 bolts on a 4 mm wall, σbr ≈ 200 MPa, FS = 3: Fb ≈ 10.7 kN per splice

10. Weight ratio to a steel tray
wFRPwsteel ≈ ρFRP · tFRPρsteel · tsteel

4 mm FRP tray versus 1.5 mm steel: (1.85×4)/(7.85×1.5) ≈ 0.63; at equal thickness ≈ 0.24

11. Side height required for a given load
Ireq = 5 w L⁴384 E · δlim

If Ireq exceeds the I of the tray in Table 1, increase the side height or reduce the support spacing.

Fittings and Accessories of Composite Cable Tray

Horizontal bend 90° and 45°Changes the direction of the FRP cable tray route, with a radius of 300 to 600 mm
Inside and outside vertical bendsChanges the height of the cable route while keeping the cable bending radius
Tee, cross and reducerBranching and width change of GFRP cable tray
Straight and expansion spliceFRP splice plate with stainless steel or composite bolts
Bracket and supportWall bracket, hanger and post made of composite profile
Hold-down clampTray clamp on the bracket for lateral restraint while allowing expansion

Installation Guide for FRP Cable Tray

  1. Supports: install the brackets at the spacing given in Table 1 and place the splices at one quarter of the span from a support.
  2. Cutting: cut the GFRP cable tray with a diamond-blade saw and seal the cut surface with resin.
  3. Drilling: make the bolt hole with a diamond or carbide bit, 1 mm larger than the bolt diameter.
  4. Joining: fasten the splices with 316 stainless steel bolts and nuts or FRP bolts and wide washers; avoid high torque.
  5. Earthing and cabling: run a separate earth conductor along the composite cable tray and secure the cables with clamps.
  6. Cover: on open routes and under falling debris, install composite covers and check the expansion joints.

Applications of Composite Cable Tray

Refineries and petrochemical plants, power plants and substations, water and wastewater treatment plants, offshore platforms and jetties, chlor-alkali and electroplating industries, mines and processing plants, tunnels and metro, food and pharmaceutical plants; wherever steel cable tray corrodes, Nabak Composite FRP cable tray and GFRP cable ladder are the lasting replacement.

What is the advantage of FRP composite cable tray over galvanized cable tray?

FRP cable tray does not rust in acidic, chloride and marine environments, is electrically insulating, has about one quarter of the density of steel and is cut and installed with simple tools and no welding; therefore its service life and life-cycle cost in a corrosive environment are much better than those of galvanized tray.

What should the support spacing of composite cable tray be?

The usual support spacing of FRP cable tray is 1.5 to 3 m and is selected from the allowable-load table according to the width, side height and weight of the cables. Trays with a 100 mm side are normally suitable at a 2 m span for most industrial applications.

Does FRP cable tray need earthing?

Composite cable tray is insulating and does not act as an earth conductor by itself; therefore a separate earth conductor must be run inside the FRP cable tray along the route.

How are FRP cable trays cut and drilled?

Cut the GFRP cable tray with a diamond-blade saw and seal the cut surface with resin; make the bolt hole with a diamond or carbide bit, 1 mm larger than the bolt diameter. Cutting and drilling are done on site, without welding or hot work.

What is the spacing of expansion joints in FRP cable tray?

The spacing of expansion joints follows L = g / (α · ΔT); with a joint gap g = 25 mm, α = 9×10⁻⁶ and ΔT = 50 °C it is about 55 m (about 42 m for steel with α = 12×10⁻⁶).

Is composite cable tray flame retardant?

Yes; FRP cable tray is made with flame-retardant resin, and its reference values are an ASTM E84 flame spread index of 25 or less (Class 1), a UL 94 V-0 flammability rating and an oxygen index of at least 30%; phenolic resin is selected for routes with low smoke and toxicity requirements. These values are industry reference ranges and must be confirmed by testing for each project.

Request a quote for FRP composite cable tray: state the type (perforated, solid-bottom, ladder), width and side height, route length, number of fittings, support spacing, cable weight and service environment.
Nabak Sazeh Gostar  |  nabakcomposite.com  |  +98 21 4881 2124  |  Instagram @nabak.composite

Disclaimer: the information in this datasheet is prepared from general and common data of the FRP and GFRP composite industry and from cable tray standards, and is provided for guidance. Nabak Composite reserves the right to modify the technical specifications of composite cable trays without prior notice.

© Nabak Composite — FRP composite cable tray and GFRP cable laddernabakcomposite.com  |  +98 21 4881 2124  |  @nabak.composite